MELSEC iQ-F Series Analog Control Module

(7/28/2017)

Analog Input Module

Model Number

FX5-4AD-ADP

FX5-8AD (*1)

Stocked Item

S

S

Certification

UL • cUL • CE (EMC)

Applicable PLCs

FX5U/FX5UC

FX5U/FX5UC (*2)

Number of Analog Input Points

4 points (4 channels)

8 points (8 channels)

Analog Input Voltage

-10 to +10 VDC (input resistance 1 MΩ)

Analog Input Current

-20 to +20 mA DC (input resistance 250Ω)

Digital Output Value

14-bit binary value

16-bit signed binary (-32000 to +32000)

Input Characteristics, Resolution (*1)

Analog Input Range

Digital Output Value

Resolution

Analog Input Range

Digital Output Value

Resolution

Voltage

0 to 10 V

0 to 16000

625 µV

Voltage

0 to 10 V

0 to 32000

312.5 μV

0 to 5 V

0 to 16000

312.5 µV

0 to 5 V

0 to 32000

156.25 μV

1 to 5 V

0 to 12800

312.5 µV

1 to 5 V

0 to 32000

125 μV

-10 to +10V

-8000 to +8000

1250 µV

-10 to +10V

-32000 to +32000

312.5 μV

Current

0 to 20 mA

0 to 16000

1.25 µA

Current

0 to 20 mA

0 to 32000

625 nA

4 to 20 mA

0 to 12800

1.25 µA

4 to 20 mA

0 to 32000

500 nA

-20 to +20 mA

-8000 to +8000

2.5 µA

-20 to +20 mA

-32000 to +32000

625 nA

Accuracy (Accuracy for the Full Scale Digital Output Value)

Ambient temperature 25 ±5°C: within ±0.1 % (±16 digit); Ambient temperature 0 to 55°C: within ±0.2 % (±32 digit)

Ambient temperature 25 ± 5˚C: within ±0.3% (±192 digits)

Ambient temperature -20 to 55˚C: within ±0.5% (±320 digits)

Conversion Speed

Maximum 450 µs (The data will be updated at every scan time of the PLC.)

Voltage/current: 1ms/ch, Thermocouple/RTD: 40ms/ch

Absolute Maximum Input

Voltage: ±15 V, Current: ±30 mA

Isolation Method

Between input terminal and PLC: Photocoupler Between input channels: Non-isolation

Number of Occupied I/O Points

0 point (This number is not related to the maximum number of I/O points of the PLC)

8

Weight (kg)

0.1

0.3

Dimensions
(W x H x D) mm

17.6 x 106 x 89.1

50 x 90 x 102.2

Notes:
For the input conversion characteristic refer to User’s Manual.
1. FX5-8AD accepts K, J, T, B, R, S type thermocouples and Pt100, Ni100 RTDs
2. FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-8AD to the FX5UC CPU module.

Analog Output Module

Model Number

FX5-4DA-ADP

Stocked Item

-

Certification

CE (EMC)

Applicable PLCs

FX5U/FX5UC

Number of Analog Output Points

4 points (4 channels)

Digital input

14-bit binary value

Analog Output Voltage

-10 to +10 VDC (external load resistance value 1k to 1 MΩ)

Analog Output Current

0 to 20 mA DC (external load resistance value 0 to 500 Ω)

Output Characteristics, Resolution (*1)

Analog Output Range

Digital Value

Resolution

Voltage

0 to 10 V

0 to 16000

625 µV

0 to 5 V

0 to 16000

312.5 µV

1 to 5 V

0 to 16000

250 µV

-10 to +10V

-8000 to +8000

1250 µV

Current

0 to 20 mA

0 to 16000

1.25 µA

4 to 20 mA

0 to 16000

1 µA

Accuracy (Accuracy for the Full Scale Analog Output Value)

Ambient temperature 25±5°C: ±0.1 % (Voltage ±20 mV, Current ±20 µA)
Ambient temperature 0 to 55°C: ±0.2 % (Voltage ±40 mV, Current ±40 µA)

Conversion Speed

Maximum 950 µs (The data will be updated at every scan time of the PLC.)

Isolation Method

Between output terminal and PLC: Photocoupler; Between output channels: Non-isolation

Number of Occupied I/O Points

0 point (This number is not related to the maximum number of I/O points of the PLC)

Weight (kg)

0.1

Dimensions (W x H x D) mm

17.6 x 106 x 89.1

Note 1: For the output conversion characteristic refer to User’s Manual.


Temperature Input Modules

Model Number

FX5-4AD-PT-ADP

FX5-4AD-TC-ADP

FX5-4LC

Stocked Item

S

S

S

Certification

UL • cUL • CE

Applicable PLCs

FX5U/FX5UC

Analog Input Points

4 points

Resistance Temperature Detector/Thermocouples

Pt100 /Ni100

K, J, T, B, R, S

Thermocouple: K, J, R, S, E, T, B, N JIS C 1602-1995, PL II, W5Re/W26Re, U, L

Resistance thermometer:

3-wire Pt100 JIS C 1604-1997

3-wire JPt100 JIS C 1604-1981

2-wire/3-wire Pt1000 JIS C 1604-2013

Temperature Measuring Range

Pt100: -200 to +850°C

Ni100: -60 to +250°C

K:-200 to +1200°C

J: -40 to +750°C

T: -200 to +350°C

B: 600 to 1700°C

R: 0 to 1600°C

S: 0 to 1600°C

K: -200 to +1300˚C (-100 to +2400˚F)

J: -200 to +1200˚C (-100 to +2100˚F)

T: -200 to +400˚C (-300 to +700˚F)

S: 0 to 1700˚C (0 to 3200˚F)

R: 0 to 1700˚C (0 to 3200˚F)

E: -200 to +1000˚C (0 to 1800˚F)

B: 0 to 1800˚C (0 to 3000˚F)

N: 0 to 1300˚C (0 to 2300˚F)

PL II: 0 to 1200˚C (0 to 2300˚F)

W5Re/W26Re: 0 to 2300˚C (0 to 3000˚F)

U: -200 to +600˚C (-300 to +700˚F)

L: 0 to 900˚C (0 to 1600˚F)

Micro voltage input: DC0 to 10mV, DC0 to 100mV

Pt100 (3-wire type): -200 to +600˚C (-300 to +1100˚F)

JPt100 (3-wire type): -200 to +500˚C (-300 to +900˚F)

Pt1000 (2-wire type/3-wire type): -200.0 to +650.0˚C (-328 to +1184˚F)

Digital Output

Pt100: -2000 to +8500°C

Ni100: -600 to +2500°C

K: -2000 to +12000

J: -400 to +7500

T: -2000 to +3500

B: 6000 to 17000

R: 0 to 16000

S: 0 to 16000

-

Accuracy

25±5°C

Pt100: ±0.8°C

Ni100: ±0.4°C

Varies according to thermocouple used. Please refer to the manual

-20 to 55°C

Pt100: ±2.4°C

Ni100: ±1.2°C

Resolution

0.1°C(0.2°F)

K/J/T: 0.1°C

B/R/S: 0.3°C

0.1˚C (0.1˚F), 1.0˚C (1.0˚F), 0.5 μV, or 5.0 μV

Varies depending on input range of used sensors.

Conversion Speed

85 ms/channel

250 ms/4ch

Isolation Method

Between input terminal and CPU module: Photocoupler Between input channels: Non-isolation

-

Number of Occupied I/O Points

0

8

Dimension (H x W x D)

106 x 17.6 x 89.1

90 x 60 x 102.2

Weight (kg)

0.1

0.3