Model CP30-BA CP30-HU
Number of poles 1 2 3 1 2 3
Rated current (A) 0.1 0.25 0.3 0.5 1 2 3 5 7 10 15 20 30 0.1 0.25 0.3 0.5 1 2 3 5
Rated
short-circuit
capacity
(kA)
UL 1077
CSA C22.2
No.235 (*6)
Rated
voltage (V)
AC (V) 250 250
DC (V) 65 125 - 65 125 -
AC 2.5kA at 250V 2.5kA at 250V
10kA at 125V
10kA at 250V
DC 2.5kA at 65V 2.5kA at 125V - 10kA at 65V 10kA at 125V -
IEC 60934
EN 60934
GB/T 17701
(*9) (Icn)
Rated insulation voltage Ui (V) 250 250
AC 2.5kA at 230V 2.5kA at 230V
10kA at 120V
10kA at 230V
DC 2.5kA at 60V 2.5kA at 120V - 10kA at 60V 10kA at 120V -
IEC 60947-2
EN 60947-2
(Icu/Ics)
Rated insulation voltage Ui (V) 250 250
AC 2.5/2.5kA at 230V 2.5/2.5kA at 230V
10/10kA at 120V
10/10kA at 230V
DC 2.5/2.5kA at 60V 2.5/2.5kA at 120V - 10/10kA at 60V 10/10kA at 120V -
AC-DC common use AC/DC compatible (*7) -(*1) AC/DC compatible – (*1)
Operating characteristics Instantaneous type (I);
Medium type (M), (MD);
Slow type (S), (SD);
Fast type (F) (*2)
Instantaneous type (I);
Medium type (M), (MD);
Slow type (S)
Body mounting method IEC 35mm rail mounting IEC 35mm rail mounting
CE marking EN 60934 : TÜV approval (*6)
EN 60947-2 : Self-declaration (*4)
EN 60947-3 : TÜV approval (*3)
EN 60934 : TÜV approval
EN 60947-2 : Self-declaration (*4)
EN 60947-3 : TÜV approval (*3)
UKCA marking EN 60934 : Self-declaration (*6)
EN 60947-2 : Self-declaration (*4)
EN 60947-3 : Self-declaration (*3)
EN 60934 : Self-declaration
EN 60947-2 : Self-declaration (*4)
EN 60947-3 : Self-declaration (*3)
CCC Certified (*4), (*6) -
Classification Society (☆ approval)
(NK, LR, ABS, DNV)
- ☆ (*5) (NK) (*8) ☆ (*5) (NK) (*8) -
    Notes:
  • *1The 3-pole products are for AC use only.
  • *2Contact us for operating characteristics other than those mentioned above.
  • *3In poles equipped with a shunt tripping mechanism, the overcurrent tripping element is not operative (switched shunt tripping).
  • *4UL (cURus), CCC, and CE, UKCA marking are displayed on standard products.
  • *5Support for special order
  • *6In case of spring clamp terminal rated 20A, it is not available.
  • *7In the case of AC/DC shared models, tripping operating characteristics differ between AC and DC.
  • *8Not supported when male tab terminal is selected for terminal shape.
  • *9CP30-BA only.